October 20, 2026
Three Moves, One Direction
The AI power story used to be a permitting story: how fast could a substation be built, how many transformers could be found, which state would say no. As of Oct. 20, 2026 it is a cost-allocation story. The three moves that day all resolved the same way. The data center ends up funding the infrastructure that connects it, and the money follows the build rather than the tariff.
Already charged to PJM residential customers
$4.4B
Transmission upgrades approved in 2024 to serve data centers across seven PJM states, Utility Dive, Oct. 1, 2025
State rate cases won since 2025
20+ in 16 states
Data center proceedings decided by regulators, Edison Electric Institute and Charles River Associates, Oct. 20, 2026
Announced large-load pipeline
$1.14T / 72 GW
Utility-disclosed large-load projects of roughly 20 MW or more, EEI project tracker, Oct. 9, 2026
Data centers' share of U.S. electricity by 2030
9-17%
Up from 4-5% in 2024, EPRI Powering Intelligence, Feb. 25, 2026
Share of PJM's 2025/26 capacity price increase
63%
Attributed to data-center demand by PJM's independent market monitor, reported June 18, 2026
- FERC, Oct. 20: the five-member commission is drafting a proposal to widen its authority over AI-driven electricity demand, having already missed the Department of Energy's April 30 deadline for national interconnection standards.
- President Trump, late Oct. 20, in a Truth Social post: new and large data centers are 'mandated by me to make their own electricity,' sell any excess back to the local grid, and pay host communities a 'dividend'.
- Edison Electric Institute, Oct. 20: electric companies are working with state regulators so that data centers pay the costs of serving them, with eight standard protections now in use across 16 states.
Federal retreat
FERC's Non-Decision Is the Signal
Washington's retreat from writing one national rule is the most consequential part of the three-day story. FERC's pending rulemaking in Docket RM26-4-000 still asks, in its own words, whether large loads should pay the full cost of the grid upgrades needed to interconnect them and how any overpayment should be credited back. It defines a large load as demand above 20 MW. That docket has not produced a rule, and FERC has missed the Energy Department's April 30 deadline for national standards.
- Oct. 9: FERC accepted PJM's 50 MW large-load definition and its registry of current and prospective loads, but rejected the Interim Resource Adequacy Service plan that would have let big loads connect while being curtailed first.
- The reason: FERC found the framework discriminated against new large loads and intruded on state authority, because it effectively set a retail rate and dictated which retail customers get curtailed.
- June 18: FERC issued Section 206 show-cause orders to all six regional grid operators, directing them to justify or rewrite their large-load tariffs within 60 days, and PJM separately promised a fast track for up to ten interconnection requests every two years.
- FERC still missed the Department of Energy's April 30 deadline for national interconnection standards, and is now drafting a proposal to expand its authority instead.
In a grid emergency, non-critical data centers should be shut off before ordinary customers — homes, hospitals, schools.
The tariff template
Utilities Have Already Written the Rules
While FERC stalled, states and utilities wrote the operative rulebook. The clearest example is Duke Energy, which on Oct. 7 reached an agreement with the North Carolina Public Staff, Amazon, Alphabet, Meta, Microsoft, the Carolina Industrial Group for Fair Utility Rates and the U.S. Department of Defense. Data centers must pay upfront for the grid facilities that serve them alone, and post deposits and security guarantees for upgrades that benefit everyone.
| Term | What the agreement requires | Applies to |
|---|---|---|
| Parties | Duke Energy Carolinas and Duke Energy Progress with the North Carolina Public Staff, Amazon, Alphabet, Meta, Microsoft, the Carolina Industrial Group for Fair Utility Rates and the U.S. Department of Defense | All North Carolina electric service agreements |
| Dedicated facilities | Nonrefundable, upfront payment for grid facilities serving only that customer, such as a substation connecting it to the grid | Large-load customers signing after June 1, 2026 |
| Shared upgrades | Upfront deposits and security guarantees for grid upgrades serving all customers, such as transmission lines | Agreements signed before June 1, 2026 already carry similar protections |
| Rate schedule | New large-load customers must take service under a 'High Load Factor' rate schedule | Loads of 50 MW or more at an 80% load factor |
| Status and price | Subject to North Carolina Utilities Commission approval, with a decision expected by mid-November 2026; contract amounts were not disclosed | Pending |
Virginia ran the same experiment a step further. A State Corporation Commission order filed July 31, 2026 requires Dominion Energy to assign the cost of transmission infrastructure directly to new large-load facilities, with mandatory contributions in aid of construction covering the substations and lines that connect a data center to the grid. The case involved a proposed $1.5 billion increase to Dominion's Rider T-1 line item, and an amended allocation factor cut the typical residential customer's monthly increase from $2.90 to $0.94, a 67.5% reduction. Dominion must file a line-extension policy amendment in a new docket within 90 days, and the commission reserved the question of extending direct assignment upstream.
| State and utility | Mechanism | Threshold and protection |
|---|---|---|
| North Carolina — Duke Energy | Settlement with the state regulator and hyperscalers | 50 MW at 80% load factor; nonrefundable upfront payment, deposits and security guarantees |
| Virginia — Dominion Energy | State Corporation Commission order, July 31, 2026 | Direct assignment of transmission cost, mandatory contributions in aid of construction, new GS-5 class at 25 MW and above under consideration |
| Ohio — American Electric Power | Approved tariff | New data centers above 25 MW pay for at least 85% of expected monthly energy even if they use less |
| Florida — NextEra Energy | LLCS-1 and LLCS-2 rate schedules, effective Jan. 1, 2026 | 50 MW or more at 85% load factor; minimum term, take-or-pay, exit fees, collateral |
| Georgia — Southern Company | Approved minimum-billing rules | Peak demand above 100 MW; longer contract terms |
| Texas — El Paso Electric | Schedule 27 proposal | 75 MW or more at 85% load factor |
| Colorado — Xcel Energy | Large-load tariff, docket 26AL-0137E | New customers or expansions of 50 MW or more |
| Maryland — FirstEnergy and Exelon utilities | Large-load rate schedule proposals filed Sept. 1, 2026 | PJM's footprint, where cost allocation now lands |
| Wyoming — LPCS | Dedicated energy-procurement model | Participants fund the incremental transmission and distribution facilities needed to serve them |
The money already moved
$4.4 Billion Is the Floor, Not the Headline
In 2024 alone, regulators approved about $4.4 billion of local transmission projects needed to bring data centers online across Illinois, Maryland, New Jersey, Ohio, Pennsylvania, Virginia and West Virginia, where utilities had initiated more than 150 such projects since 2022 and nearly half the money landed in Virginia. Those costs reached residential bills because PJM's transmission planning treats data-center projects as informational, and state reviews of retail rates never saw them. PJM's independent market monitor has since estimated data centers drove 63% of the price increase in the 2025/2026 capacity auction, worth about $9.3 billion to ratepayers, on an auction that cleared at a record $329.17 per MW-day.
Data centers' share of electricity consumed, U.S. and Virginia
EPRI's Powering Intelligence scenarios, published Feb. 25, 2026. Virginia is the live case: more than a fifth of its electricity today, potentially more than half by 2030.
Unit: % of electricity consumed
U.S. today, 2024
Range of 4-5% today
5%
U.S. 2030, low scenario
EPRI low growth case
9%
U.S. 2030, high scenario
EPRI high growth case
17%
Virginia today
More than 20% today
20%
Virginia 2030, low scenario
EPRI low growth case
39%
Virginia 2030, high scenario
EPRI high growth case
57%
| Utility | Counterparty | Announced scale |
|---|---|---|
| Entergy, Louisiana unit | Meta | $50 billion, 5 GW planned at Richland Parish |
| Entergy, Arkansas unit | Digital infrastructure developer | $6 billion; 150 MW in 2027, up to 1,000 MW with expansion |
| American Electric Power, Ohio unit | Amazon | 100 MW of on-site fuel-cell generation contracted with two large customers in New Albany |
| ONEOK, Oklahoma Gas & Electric | Alphabet | $9 billion; roughly 1,000 MW by 2031 and 1,200 MW by 2036 |
| FirstEnergy, Potomac Edison | Quantum Frederick project | 2,400 MW |
| PPL Electric Utilities | PowerHouse Data Centers | 1,350 MW across three campuses |
| DTE Energy | OpenAI and Oracle | $7 billion campus with 1,400 MW in Saline Township, Michigan |
| Ameren, Missouri unit | Alphabet | $15 billion project |
| Equinix with ComEd | Interconnection in Illinois | 700 MW |
Where the money lands
Grid Construction Leaves the Rate Base
This is the layer the AI-power trade has missed. Cost-allocation reform moves grid construction off utility rate base and onto private balance sheets: when a data center prepays for its substation, the utility recovers its cost without funding construction itself and then billing other customers for it. The flow of money tilts toward whoever gets paid for building and equipping the grid, and away from utilities whose earnings growth depended on data-center load flowing into rate base. Quanta Services carries a $53.4 billion backlog after $9.56 billion of second-quarter revenue, up 41% year over year; Vertiv grew revenue 24% to $3.27 billion at a 37.7% gross margin; GE Vernova posted $11.10 billion of second-quarter revenue across power, wind and electrification.
Who must fund the AI build from internal cash: capital spending versus operating cash flow
Trailing twelve months through each company's June 30, 2026 quarter. Above 1.0x means the build is being financed outside operating cash, which is precisely why utilities are pushing customers to prepay and hyperscalers are being asked to self-fund.
Unit: x (capex divided by operating cash flow)
Widest funding gap among the utilities here
2.3
5 GW of announced Meta load in Louisiana
1.5
Customer prepayments relieve this gap
1.4
Trailing free cash flow negative $11.6B
1.1
Trailing free cash flow positive $53.3B
0.7
Paid on build volume, not on tariffs
0.3
Equipment content per megawatt
0.1
The strain lands where the build is biggest. Dominion Energy spends 2.27 times its operating cash flow on capital, Entergy 1.52 times and Duke Energy 1.37 times. Amazon is the only hyperscaler here running negative trailing free cash flow, at negative $11.6 billion, against Alphabet at positive $53.3 billion. Utilities in the middle of the largest data-center build-outs cannot fund it from internal cash, which is why they now insist the customer pays upfront and why the tariff template is a financing tool rather than a fairness gesture.
- HD Hyundai Electric reported an order backlog of $8.5 billion at the end of June 2026, up 23% in six months, and won a 765 kV extra-high-voltage transformer and reactor order in the USA valued at 173 billion won in May 2026.
- Upstream of that sits the physical queue: US utilities are scrambling for transformers and switchgear as data-center demand strains supply, soequipment lead times now cap how fast any tariff can work.
Horizons
Two Calendars Decide the Answer
There are two clocks running, and they are not the same clock. The docket calendar decides who pays in a specific state, in a specific month. The load forecast decides how much power is being repriced over a decade. Investors should track both, because the first is what changes utility rate cases and project economics, while the second is what changes the multiple on the equipment suppliers.
- Next days to quarters: the North Carolina Utilities Commission ruling on the Duke Energy settlement, expected by mid-November 2026.
- Next days to quarters: Dominion Energy's mandatory contribution-in-aid-of-construction filing, due within 90 days of the final order, with upstream transmission cost allocation still reserved.
- Next days to quarters: PJM's compliance filing directed by FERC's Oct. 9 order, and the six regional operators' responses to FERC's 60-day show-cause orders.
- Next days to quarters: Senate action on the Ratepayer Protection Act, which passed the House 417-3 on Sept. 16, 2026 and would set full-incremental-cost standards for loads above 100 MW.
- One to three years: data centers taking 9-17% of U.S. electricity by 2030, with Virginia moving from more than 20% to as much as 57%.
- One to three years: self-generation normalizing, as hyperscalers are told to make their own power and sell excess back to the local grid.
- One to three years: sitage migrating toward states with the cheapest large-load tariff rather than the fastest permitting, which redistributes load toward the South and Mountain West.
- One to three years: litigation risk on FERC's expanded authority, which policy analysts expect states to challenge.
Stress test
What Would Break This Read
Three things could break the cost-allocation conclusion, and each is checkable. The evidence base is not neutral: the study utilities lean on was commissioned by their trade group, and PJM's independent market monitor reaches the opposite conclusion. The dollar amounts behind the biggest template are not public. And most of the pipeline is announced rather than contracted.
- The utilities' evidence is industry-commissioned. Charles River Associates was retained by the Edison Electric Institute, and its conclusion that data centers lower rates for other customers is a utility-side finding rather than an independent one, while PJM's market monitor calls the existing cost allocation rules unjust and unreasonable.
- Contract amounts in the Duke Energy settlement were not disclosed, so the size of the cash shift to customer prepayments remains an estimate rather than a reported figure.
- Much of the $1.14 trillion and 72 GW is announced rather than contracted, and FERC's own decision to leave curtailment priority to the states means the eventual rulebook is still being written.
Where the AI power bill actually lands
- Backlog of $53.4 billion and second-quarter revenue of $9.56 billion, up 41% year over year, put grid construction demand ahead of the tariff fights.
- Customer-funded grid spending lands directly in the order book rather than in contested rate cases.
- Near term, faster interconnection once states approve large-load tariffs; over one to three years, transmission build set by 9-17% national electricity share by 2030.
- Risk: construction carries a 14.4% gross margin, so cost inflation on grid work eats contract gains.
- FERC's rejection of PJM's curtailment-first plan could keep capacity prices higher for longer, which Jefferies called favorable to merchant generators.
- 32,400 MW of owned capacity is the natural counterparty if hyperscalers shift to buying firm power.
- Near term, PJM's compliance filing and the next capacity auction; over one to three years, power-purchase demand from self-generation mandates.
- Risk: net debt of 2.96 times EBITDA leaves the balance sheet sensitive to any demand slowdown.
- Second-quarter revenue rose 24% to $3.27 billion with a 37.7% gross margin, and trailing operating margin is 20.4%.
- Behind-the-meter generation for data centers adds power management and thermal content per megawatt rather than subtracting it.
- Near term, order intake tied to tariff-driven projects; over one to three years, 9-17% national electricity share by 2030.
- Risk: a 20.4% trailing operating margin leaves limited cushion if project timing slips.
- Order backlog of $8.5 billion at the end of June 2026, up 23% in six months, plus a 765 kV U.S. transformer and reactor order valued at 173 billion won in May 2026.
- Transformer and switchgear shortages cap how quickly any large-load tariff can deliver megawatts, which is this supplier's pricing power.
- At499,000 won the shares sit near the 473,500 won 52-week low after peaking at 1,430,000 won.
- Over one to three years, grid build scales with data-center load share of 9-17% of U.S. electricity by 2030.
- The Oct. 7 settlement would have customers prepay for dedicated grid facilities, cutting the utility's own funding need for data-center construction.
- Rate-base growth slows as customer-funded assets replace regulated investment, so volume growth no longer converts one-for-one into earnings growth.
- Near term, the North Carolina Utilities Commission decision expected mid-November 2026; over one to three years, a federal ratepayer standard would export the template.
- Support: second-quarter 2026 net income of $1.09 billion and a 1.37 times capex-to-operating-cash-flow gap that customer prepayments would help fill.
- Capital spending runs 2.27 times operating cash flow, the widest funding gap among the utilities here, while second-quarter net income fell 58% year over year to $340 million.
- The Virginia order shifts transmission cost onto large loads but shrinks the residential base that funds the grid.
- Near term, the 90-day contribution-in-aid-of-construction filing and the unresolved question of upstream cost allocation.
- Over one to three years, leverage of 6.95 times EBITDA constrains a build that customers, not ratepayers, must now finance.
- Trailing capital spending of $173.0 billion exceeds trailing operating cash flow of $161.4 billion, leaving free cash flow at negative $11.6 billion.
- Signing the Duke Energy settlement converts socialized grid cost into prepaid capital, and the community dividend adds to it.
- Near term, third-quarter results and capex guidance; over one to three years, self-generation directives duplicate utility-scale power build inside the customer's own balance sheet.
- Risk to the bear case: $135.3 billion of trailing net income absorbs the shift, so the exposure is capital intensity rather than solvency.
- Trailing operating cash flow of $185.7 billion covers capital spending of $132.4 billion with $53.3 billion of free cash flow left, so the same cost shift lands without balance-sheet strain.
- Google's Oklahoma contract has it paying 100% of grid connection costs and its share of required generation.
- Near term, third-quarter capex guidance; over one to three years, firm-power and self-generation agreements displacing utility tariffs.
- Risk: a 33.1% trailing operating margin leaves little room if power costs are passed through rather than absorbed.